Brand Name : ELTEK
Model Number : Flatpack2 48V-60V/2000W HE
Place of Origin : CHINA
MOQ : 1pc
Payment Terms : T/T, Western Union, MoneyGram
Supply Ability : 500pcs/week
Delivery Time : 3-7 work days
Packaging Details : 1pc into a spare inner foam carton and pack with exteral wooden carton
Type : power module
Products status : Stock
Product name : 241115.705
Shipping term : DHL,Fedex,UPS,EMS,AIR
Condition : Brand New
Warranty : Six month
ELTEK Flatpack2 48V-60V/2000W HE 241115.705 rectifier module
Product Description:
The Flatpack2 48-60/2000 HE is a cost efficient rectifier for 48V and 60V lead acid battery systems as well as 48V NiCad.
| Model | 48-60/2000 HE |
| Part number | 241115.705 |
| INPUT DATA | |
| Voltage (nominal) | 185 - 275 VAC / 185 - 275 VDC |
| Voltage (operating range) | 85 - 300 VAC / 80 - 300 VDC |
| Current (maximum) @ nominal input, full load | 11.6 ARMS |
| Frequency | 45 - 66 Hz / 0 Hz |
| Power Factor | > 0.99 at 50% load or more |
| THD | < 5% at 100% load |
| Protection | Fuse in L & N, Varistor, Shutdown when input voltage is out of operating range |
| OUTPUT DATA | |
| Voltage (default) 1) | 53.5 VDC (67 VDC in 60V mode) |
| Voltage (adjustable range) 1) | 39.9 - 72 VDC |
| Power (maximum) @ nominal input | 2000 W (@VOUT ≥ 48VDC) |
| Power @ 85 VAC | 750 W |
| Current (maximum) @ nominal input | 41.6 A (@VOUT < 48VDC) |
| Hold up time, 1500W output power | >20ms; output voltage > 53.5 VDC (60V mode) |
| Current sharing (10 - 100% load) | ±5% of maximum current from 10 to 100% load |
| Static Voltage regulation (10 - 100% load) | ±0.5% |
| Dynamic Voltage regulation | ±5.0% for 10-80% or 80-10% load variation, regulation time < 50ms |
| Ripple & noise | < 150 mVPP , 30 MHz bandwidth / < 2 mVRMS psophometric |
| Protection | Fuse , Short circuit proof, High temperature protection, Over voltage Shutdown |
| OTHER SPECIFICATIONS | |
| Efficiency | 96.2 % |
| Isolation | 3.0 kVAC - input to output, 1.5 kVAC - input to earth, 500 VDC - output to earth |
|
Alarms: Red LED | Low / high input voltage shutdown, High / low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low output voltage alarm, CAN bus failure |
| Warnings: Yellow LED | Rectifier in power de-rate mode, Remote output current limit activated, Input voltage out of range, flashing at overvoltage, Loss of CAN communication with controller |
| Normal operation: Green LED | |
| MTBF (Telcordia SR-332 Iss.I method III (a)) | >350 000 (@ Tambient : 25 °C) |
| Operating temp. (5-95% RH n.cond. hum.) | -40 to + 75°C [-40 to +167°F] |
| Max output power de-rates above temp / to | 45°C [113°F] / 1200W @ 75°C[167°F] |
| Storage temperature | -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing |
| Dimensions[WxHxD] / Weight | 109 x 41.5 x 327mm (4.25 x 1.69 x 13”) / 1.950 kg (4.3lbs) |
| DESIGN STANDARDS | |
|
Electrical safety | EN 62368-1:2020+A11:2020, IEC 62368-1:2018, IEC 60950-1:2005+A2:2013 UL 62368-1:2019 , CSA C22.2 No.62368-1:2019 |
| EMC | EN IEC 61000-6-1:2019, -6-2:2019, -6-4:2019, IEC 61000-6-5: 2015 EN 61000-6-3:2007 + A1:2011/AC:2012, ETSI EN 300 386:2020 |
|
Environment | ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS), 2012/19/EU (WEEE), IEC 63000:2018, EN IEC 62474:2019 Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised |